Wire Size for Home Appliances (AC, Geyser, EV Charger, Pump)

A quick chart of the recommended copper house-wire size and MCB for common home appliances.

Download PDF

Matching the wire size to the appliance keeps circuits cool and safe. This chart gives a starting-point copper conductor size and MCB rating for common household loads on a 230 V single-phase supply. For an exact figure by load and run length, use the wire-size calculator.

Appliance / circuitTypical loadCopper wireMCB
Lighting & fans≤ 800 W1.0 sq mm6 A
5 A socket points≤ 1,100 W1.5 sq mm10 A
15 A power sockets≤ 2,900 W2.5 sq mm16 A
Geyser / water heater (2 kW)2,000 W2.5 sq mm16 A
Geyser / water heater (3 kW)3,000 W4 sq mm20 A
Air-conditioner (1–1.5 ton)~1,800 W2.5 sq mm16 A
Air-conditioner (2 ton)~2,500 W4 sq mm20 A
Kitchen appliance / microwave≤ 3,000 W2.5–4 sq mm16–20 A
Submersible pump (1 HP)~1,100 W2.5 sq mm16 A
EV home charger (3.3 kW)3,300 W4 sq mm20 A
EV home charger (7.4 kW)7,400 W6 sq mm40 A

Size up for long runs, high ambient temperature or bunched cables. Browse matching APAR house wires.

Guidance only. Figures follow common Indian domestic practice (IS 732 / IS 694), assume copper conductors unless stated, and depend on run length, grouping, ambient temperature and installation. Always have the final design confirmed by a licensed electrician.