Solar DC Cable Chart: Sizes, Resistance & Current Ratings (BS EN 50618)

E-beam XLPO solar cable from 2.5 to 300 sq mm — construction, DC resistance, diameter and current ratings at 60°C.

Share

Reference data for APAR e-beam irradiated, annealed tinned copper (ATC) / XLPO solar PV cable to BS EN 50618:2014 (H1Z2Z2K), rated 1.5 kV DC (maximum 1.8 kV) and 120°C continuous operation.

Size (mm²)Construction (No./dia mm)DC resistance 20°C (Ω/km)O.D. (mm)At 60°C in air (A)Single cable on surface (A)2 cables adjacent (A)
2.550/0.268.215.1413933
456/0.315.095.6555244
684/0.313.396.1706757
1080/0.411.957.5989379
16126/0.411.248.8132125107
25196/0.410.79510.9176167142
35276/0.410.56512.2218207176
50396/0.410.39313.8276262221
70360/0.510.27716.0347330278
95475/0.510.2117.8416395333
120608/0.510.16419.8488464390
150760/0.510.13222.2566538453
185925/0.510.10824.9644612515
2401221/0.510.081728.0775736620
3001525/0.510.065430.5895850716

The conductor is class 5 flexible tinned copper — tinning protects against oxidation over the 25-year-plus outdoor life, which is why the resistance values sit roughly 2% above the bare-copper IS 8130 maxima. That is correct, not a defect.

Full specifications, certifications (IEC 62930:2017, UL 4703, TÜV) and the aluminium variant are on the solar cables product page. Sizing method: see our Rooftop Solar Cable Sizing Guide.