MVCC Drum Handling, Storage and Site Receipt Checklist

Protect covered conductor between the factory and the pole top.

Share

Most damage to a covered conductor happens before stringing starts. A drum dropped from a truck, rolled the wrong way across rough ground or left unsealed in the rain can damage the covering or let moisture into the conductor, and the defect may not show until the line is in service. The covering is what the utility is paying for, so the drum deserves the same care as the conductor on it.

Site receipt checklist

CheckAccept when
Drum identificationDrum number, conductor type, size, voltage grade and length match the delivery note and purchase order
Test documentsRoutine test certificates are received for each drum, cross-referenced by drum number
Drum structureFlanges unbroken, battens or lagging intact, spindle holes clear
Conductor endsBoth ends sealed with end caps and secured to the drum
Outer layersNo visible cuts, crushing or nail damage on the outermost turns
MarkingPrinted marking on the covering is legible and matches the order

Record any damage on the delivery note before signing, with photographs, and keep the drum aside until it has been assessed.

Unloading

Drums should be lifted with a crane or forklift using a spindle through the centre hole, or lowered down a ramp under control. They should never be dropped from the vehicle onto the ground or onto tyres. A forklift should lift under both flanges, never against the conductor or lagging.

Rolling and storage

  • Roll a drum only in the direction of the arrow painted on the flange, so the turns do not loosen.
  • Store drums standing on their flanges on firm, level, well-drained ground, chocked so they cannot roll. Do not lay them flat.
  • Keep end caps in place throughout storage. Replace any cap removed for inspection, and reseal a cut end the same day.
  • Store away from fire risk, chemical spillage and vehicle traffic, and keep enough space between drums for lifting equipment.
  • Use stock in delivery order, and keep the test certificates with the drum records.

At the stringing site

Mount the drum on a stand with a brake so the conductor pays out under controlled back-tension and does not touch the ground. Inspect each section as it leaves the drum. Stringing practices, clamps and connectors that protect the covering are covered in the MVCC accessories and installation guide, and the clauses to include in a purchase specification are in the covered conductor tender checklist.