A wiring clause that reads “FRLS copper wire of approved make” cannot be enforced. It names no grade, no standard and no measurable property, so the lowest-cost product that fits the words can be supplied and nobody can show that it fails the specification. This guide lists what a house-wire clause in a specification or bill of quantities should state, with a template that can be adapted. It is written for architects, consultants and project engineers.
What the clause should state
| Clause element | What to write | Why it matters |
|---|---|---|
| Standard and marking | The Indian Standard by number and year, with the ISI mark and the BIS licence number printed on the wire | APAR house wires are made to IS 694:2010 and carry the grade, size, 1100 V, the standard and the BIS licence number in the printing along the wire |
| Voltage grade | 1100 V | The grade stated on all six APAR house-wire product pages |
| Conductor | Annealed bare copper of electrolytic grade, with the conductor class where it matters | APAR house wires use flexible stranded copper. Anushakti HR FR LSH is published in both Class 2 and Class 5 |
| Insulation grade | The grade by its full name: FR PVC, FR-LSH, HR FR PVC, HR FR-LSH or HFFR | “FRLS” is used loosely in the trade and covers several different products |
| Fire properties | Oxygen index, temperature index, smoke density and acid gas values to be declared by the manufacturer | These four figures appear on each product page and allow two offers to be compared |
| Sizes | The size for each circuit type, in sq mm | Not every grade is published in every size (see the table below) |
| Colours | The colour for phase, neutral and earth | Avoids site substitution of whatever colour is in stock |
| Documents | Product datasheet with the offer, and the manufacturer’s test certificate with the delivery | Gives the site engineer something to check the delivery against |
Low halogen is not halogen-free
LSH means low smoke, low halogen. A low-halogen grade is not halogen-free. Where the project requires halogen-free insulation, as is common for hospitals, schools, high-rise towers and data centres, the clause should ask for HFFR by name. In the APAR range the halogen-free house wire is Anushakti Fire Protekt EBXL HFFR.
APAR grades and published sizes
| Insulation grade | APAR product | Published sizes (sq mm) |
|---|---|---|
| FR PVC | Shakti FR PVC | 0.75 to 16 |
| FR-LSH | Shakti FR LSH | 0.5 to 16 |
| HR FR PVC (e-beam) | Anushakti HR FR PVC | 0.5 to 16 |
| HR FR-LSH (e-beam) | Anushakti HR FR LSH | 0.75 to 6 |
| HR FR-LSH, lead-free | Green Wire HR FR LSH PVC | 0.5 to 6 |
| HFFR (e-beam) | Anushakti Fire Protekt EBXL HFFR | 0.75 to 6 |
A specification that calls for a grade published only up to 6 sq mm needs a separate line for sub-mains and other circuits above that size. The side-by-side comparison of the six products is in the APAR house wire range at a glance chart.
Template clause
The wording below is a template. The items in square brackets are for the specifier to complete.
“Wiring shall be carried out with single-core, 1100 V grade, [grade by full name] insulated wires with annealed bare copper conductors, conforming to [standard number and year], bearing the ISI mark with the BIS licence number printed on the wire. Sizes shall be [size] sq mm for lighting circuits, [size] sq mm for socket circuits and [size] sq mm for [appliance] circuits. The manufacturer shall declare the oxygen index, temperature index, smoke density and acid gas values of the insulation. Wires shall be of [named product and manufacturer] or an equivalent approved in writing, equivalence being judged on the declared grade, standard and fire properties. The product datasheet shall be submitted for approval before procurement and the manufacturer’s test certificate shall accompany each delivery.”
Defining “or equivalent”
The phrase “or equivalent” is where most substitution happens. It is safer to define equivalence in the clause itself: the same insulation grade by name, the same standard, and declared fire properties no worse than the product named. An offer that cannot produce a datasheet with those figures is not equivalent.
This guide covers the wire clause only. Circuit design, protection and earthing are separate clauses and remain the responsibility of the electrical designer.