Skip to main content

Cable Voltage-Drop Reference Table

Voltage-drop values (mV/A/m) for copper house wires, with the 3% limit and a worked example.

Download PDF

Long cable runs lose voltage. Keep the drop within about 3% of supply voltage (≈ 6.9 V on a 230 V circuit). Use the values below with this formula:

Voltage drop (V) = (mV/A/m × Current A × Length m) ÷ 1000

Conductor size (sq mm)Approx. voltage drop (mV/A/m)
1.044
1.529
2.518
4.011
6.07.3
104.4
162.8
Indicative single-phase copper values for guidance. Confirm against the APAR datasheet for exact conductor resistance.

Worked example

A 2.5 sq mm wire carrying 20 A over a 30 m run: 18 × 20 × 30 ÷ 1000 = 10.8 V — that is 4.7% of 230 V, over the 3% limit. Step up to 4 sq mm: 11 × 20 × 30 ÷ 1000 = 6.6 V (2.9%) — within limit.

For an instant check across sizes, loads and run lengths, use the APAR Wire-Size Calculator, which applies both ampacity and the 3% voltage-drop rule for you.
Take this with you. Download the printable PDF version of this reference.
Download PDF