Overfilling a conduit traps heat and makes wire-pulling damage the insulation. Good practice is to fill a conduit to no more than about 40% of its cross-section. The chart below gives the approximate maximum number of single-core PVC house wires per conduit size.
| Conduit size | 1.0 sq mm | 1.5 sq mm | 2.5 sq mm | 4.0 sq mm | 6.0 sq mm |
|---|---|---|---|---|---|
| 20 mm | 11 | 10 | 6 | 5 | 3 |
| 25 mm | 18 | 15 | 11 | 8 | 6 |
| 32 mm | 31 | 27 | 19 | 14 | 10 |
| 40 mm | 51 | 45 | 31 | 23 | 17 |
| 50 mm | 81 | 70 | 49 | 36 | 27 |
The rule in short
Usable conduit area = conduit internal cross-section × 0.40. Number of wires ≈ usable area ÷ overall area of one wire. Remember that more wires bunched together also means you must derate their current rating (see the ampacity chart).