Covered Conductor Glossary: Terms Used in Tenders and Datasheets

Every covered conductor term a tender or datasheet uses, defined in one table.

Share

Covered conductor tenders and datasheets use a mix of conductor, insulation and hardware terms, and the same term is sometimes used loosely. This glossary defines the terms a buyer meets when specifying medium voltage covered conductor (MVCC), so that the specification, the quotation and the test certificate all refer to the same thing.

TermMeaning in a covered conductor specification
Covered conductor (MVCC)A stranded overhead conductor with a semi-conducting screen and insulating layers extruded over it. The covering limits the faults caused by brief contact with branches, other phases and animals. It is not rated as a full insulated cable, so the line is still supported on insulators and clamps.
AAACAll aluminium alloy conductor. One of the four core types APAR lists for covered conductor.
ACSRAluminium conductor steel reinforced. Aluminium strands over a steel core that carries much of the mechanical load.
ACSSAluminium conductor steel supported. Annealed aluminium strands over a steel core, used where the conductor operates at higher temperature.
AL59 ACSThe high-temperature core option on the APAR page, rated up to 105°C against up to 95°C for the other core types.
Longitudinally water-tight conductorA stranded conductor built so that water cannot travel along the strands if the covering is damaged.
Semi-conducting screenThe layer between the conductor and the inner insulation. It smooths the electric field at the conductor surface.
Inner insulationThe XLPE layer over the screen, described on the APAR page as carbon free.
Outer insulationThe UV-protected, anti-tracking black layer of XLPE or HDPE on the outside.
TrackingThe formation of a conductive path across an insulating surface under contamination and moisture. An anti-tracking outer layer is designed to resist it.
SpanThe horizontal distance between two supports on the line.
SagThe vertical drop of the conductor below the line joining its two supports. Sag and tension together set ground clearance.
Messenger wireA separate supporting wire that carries the load of a bundled or spacer cable system. Covered conductor is self-supporting and does not need one.
Rated tensile strength (RTS)The breaking load of the conductor as declared in the datasheet, used to set the permitted working tension.
AmpacityThe current a conductor can carry continuously without exceeding its rated temperature.
Suspension clampThe fitting that holds the conductor on an intermediate support.
Anchoring (dead-end) clampThe fitting that takes the full line tension at the end of a run or at an angle.
Insulation-piercing connectorA connector whose teeth pierce the covering to make contact with the conductor, so the covering does not need to be stripped. Types listed by APAR are covered-to-covered, bare-to-covered and tapping.
Arc protection deviceA fitting that holds a fault arc away from the conductor so that the arc does not burn through it at a fixed point.
Type test and routine testA type test proves a design once. A routine test is carried out on production. A certificate should state which one it records.

Standards named on the APAR page

The product page lists SS-EN 50397-1 for the covered conductor, with BS EN 50182, IS 398 Part 2 and Part 4 and IEC 61089 for the conductor, and EN 50397-2 for the accessories. The page advises confirming the applicable standard against the project tender. The covered conductor selection guide and the core options comparison use these terms in context.