LV XLPE Cable Current-Rating Chart (Copper, IS 7098 Part 1)

Copper conductor DC resistance, current ratings in ground and air, and 1-second short-circuit ratings — 4 to 1000 sq mm.

Share

Reference ratings for single-core, 1100 V XLPE insulated copper power cables to IS 7098 Part 1. Ground ratings assume 30°C ground temperature; air ratings assume 40°C ambient. For other conditions, apply the factors in our MV & LV cable derating factors chart.

Size (mm²)Max DC resistance at 20°C (Ω/km)Direct in ground 30°C (A)In air 40°C (A)Short circuit 1 s (kA)
44.6147410.57
63.0858520.86
101.8377711.43
161.1598942.29
250.7271261263.56
350.5241501545.00
500.3871771877.15
700.26821623810.01
950.19326030313.58
1200.15329535417.16
1500.12432940321.45
1850.099137146826.45
2400.075442755334.32
3000.060147763442.90
4000.04753773757.25
5000.036659884471.50
6300.028366196190.10
8000.02217211077114.4
10000.01767721188143.00

Every resistance value in this table matches the IS 8130 / IEC 60228 maximum for its size. Aluminium conductor variants are available from 16 mm² upward — see the LV XLPE power cables page for the full aluminium and copper table, armoured and unarmoured.

Related: High ampacity 105°C XLPE carries up to 15% more current from the same cross-section in hot environments.