MV & LV Cable Derating Factors: Depth of Laying & Temperature

Multiply the catalogue rating by these factors for your actual depth, ground temperature and air temperature.

Share

Catalogue current ratings assume standard conditions: 900 mm laying depth, 30°C ground, 40°C air. Real installations differ, so the rating must be multiplied by correction factors. These are the factors used for APAR MV XLPE cables (3.3 kV to 33 kV); LV practice is similar.

Depth of laying (direct in ground)

Depth (mm)3.3–11 kV single core ≤1853.3–11 kV single core >1853.3–11 kV three core22/33 kV single core ≤18522/33 kV single core >18522/33 kV three core
9001.001.001.00
10500.990.980.981.001.001.00
12000.970.960.970.990.980.99
15000.950.940.950.970.960.97

Ground temperature (90°C conductor)

Ground temp (°C)1520253035404550
Factor (direct or in duct)1.121.081.041.000.960.910.870.82

Ambient air temperature (90°C conductor)

Air temp (°C)2530354045505560
Factor1.141.101.051.000.950.890.840.77

Note what the air row implies: at a 50°C summer ambient a conventional 90°C cable keeps only 89% of its rating, and at 55°C only 84%. This is exactly the problem 105°C high-ampacity XLPE is designed for — raising the conductor limit recovers the lost margin. Factors for soil resistivity and cable grouping are available from our technical team on request.