Yes. In a single-phase circuit, every ampere that leaves through the phase wire returns through the neutral. The two wires carry the same current, so they need the same cross-section. A circuit wired with a 2.5 sq mm phase needs a 2.5 sq mm neutral.
A thinner neutral becomes the hottest wire in the conduit, and its insulation ages faster than the rest of the circuit. A second point matters as much as size. Each circuit should have its own neutral. When two circuits share one neutral, that wire can carry the current of both while each MCB sees only its own circuit. Where the two circuits sit on separate RCCBs, those devices also trip without an obvious cause.
The earth wire follows a different rule and may be sized differently. All APAR house wire grades are single-core, so phase and neutral are bought in the same size and in different colours.