Fibre Optic Link Loss Budget Guide: Attenuation, Splices and Connectors

Add up the losses before the cable is laid.

Share

A fibre link works only if enough light reaches the receiver. A loss budget adds up everything that removes light along the route and compares the total with what the equipment can tolerate. Doing the sum before laying the cable avoids a link that tests as unusable after installation.

The formula

Total link loss (dB) equals fibre loss plus connector loss plus splice loss plus design margin.

TermHow to calculate itWhere the value comes from
Fibre lossRoute length in km multiplied by attenuation in dB per kmThe fibre datasheet, at the wavelength in use
Connector lossNumber of connector pairs multiplied by loss per pairThe connector supplier
Splice lossNumber of splices multiplied by loss per spliceThe splicing method and the splice machine records
Design marginA reserve for repairs, ageing and temperatureThe network designer, commonly a few decibels

Compare with the equipment budget

The equipment maker gives a power budget, which is the difference between transmitter output and receiver sensitivity. The total link loss must stay below that figure. A link that is close to the limit on paper will fail as soon as a repair splice is added.

Worked example with assumed values

The figures below are assumed for the arithmetic and are not APAR ratings. Use the datasheet values for the fibre actually supplied.

ItemAssumed valueQuantityLoss (dB)
Fibre, single-mode0.4 dB per km20 km8.0
Connector pairs0.5 dB each21.0
Splices0.1 dB each80.8
Design margin3.0 dB13.0
Total link loss12.8

In this example the equipment power budget must be at least 12.8 dB. If it is lower, shorten the route, reduce the number of splices and connectors, or choose equipment with a larger budget.

Ways to keep the loss down

Choose cable lengths that reduce the number of joints, since each splice adds loss. Keep to the bend radius stated on the cable datasheet, because tight bends add loss. Single-mode fibre suits long routes because of its lower attenuation, while multi-mode suits shorter campus and in-building runs. APAR’s single-mode and multi-mode fibre page covers both types. For choosing a cable construction for the route, see the fibre optic cable selection guide.